Critical Power
Server Racks | Enclosures
Rackmount Accessories
Non-Rackmount Products
Miscellaneous

Minuteman® PRO-LCD Series Line Interactive UPS Specifications


System Specfications
Model PRO500LCD
PRO700LCD PRO1100LCD PRO1500LCD
VA•Watts 500 • 350 700 • 490 1100 • 770 1500 • 1050
Topology Line-Interactive, Simulated Sine Wave
Input
Number of Phase Single (1ø 2W +G)
Nominal Voltage 120VAC
Acceptable Input voltage 0 - 160VAC
Voltage Range 90 - 150VAC
Frequency Limits 50 or 60 Hz, +/-5Hz, autosensing
Low Voltage Transfer Point 90V resets to Utility Power at 94V or higher
High Voltage Transfer Point 150V resets to Utility Power at 146V or lower
Input Protection Resettable Circuit Breaker
Output (non-battery operation)
Voltage range 104 - 132VAC
Voltage Regulation 120VAC: -13.3% - +10.0%
Frequency Range 60Hz: 55 - 65Hz or 50Hz: 45 - 55Hz
Efficiency (Line Mode) >90% (Full Load)
Output (battery operation)
Waveform Type Simulated Sine Wave (Step Wave)
Nominal Voltage 120VAC
Voltage Regulation Nominal +/-5% (until Low Battery Warning)
Frequency 50/60Hz, +/-0.5Hz (unless synchronized to utility)
Transfer Time 6 ms Typical
Overload Capacity AC Mode: 110% for 5-seconds then fault, 120% Shutdown Immediately
DC Mode: 110% for 10-seconds then shutdown, 120% Shutdown Immediately
Protection Over-Current, Short-Circuit Protected and Latching Shutdown
Regulatory Compliance
Safety and Approvals cTUVus (conforms to UL1778, CSA 22.2 standards)
EMC Verification FCC Class B, CE certified
Battery System
Battery Type Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid
Typical Recharge Time From Full load dishcarge: 4-hours to 80%, 8-hours to 90%
Typical Battery Life 3 to 5 years. Environmental factors do affect battery life.
High temperatures, poor utility power, and frequent, short
duration discharges have a negative impact on battery life.
Battery Module Part # BM0048 BM0049 BM0050 BM0051
Runtime: Full Load (minutes) 5 7 7 5
Runtime: Half Load (minutes) 17 21 21 17
Surge Protection and Filtering
Surge Energy Rating 760 J
Surge Current Capability 10000 Amps total (one time 8 to 20us waveform)
Surge Response Time 0 ns (instantaneous) normal mode; <5 ns common mode
Surge voltage let-through (as a percentage
of an applied ANSI C62.41 Cat. A +/-6 kV)
< 11%
10/100 Base-T surge protection let-through
(as a percentage of an applied +/-6 kV 1.2/50
us, 500 a 8/20 uS test)
< 5%
Telephone line surge protection let-through
(as a percentage of an applied +/-6 kV 1.2/50
us, 500a 8/20 uS test)
< 1%
Noise Filter >45db normal and common mode EMI/RFI suppression
Audible Noise at 1 m (3 ft.) <45 dBA
Environmental
Operating Temperature
Operating Elevation
0 to 40 degrees C (+32 to +104 degrees F) at
0 to 1,500m (0 to +5,000 ft)
Operating Temperature
Operating Elevation
0 to 35 degrees C (+32 to +95 degrees F) at
1501 to 3,000m (0 to +10,000 ft)
Storage Temperature -15 to +45°C (+5 to +113°F)
Operating/Storage Humidity 95% Non-Condensing
Storage Elevation 0 to 15,000m (0 to +50,000 ft)
Physical
Size - Net
L X W X H
11.81 x 6.69 x 7.87"
300 x 170 x 200 mm
14.56 x 6.69 x 7.87"
370 x 170 x 200 mm
Weight - Net 17.6 lbs
8.0 Kgs
23.8 lbs
10.8 Kgs
34.2 lbs
15.5 Kgs
39.2 lbs
17.8 Kgs
Size - Shipping
L X W X H
15.16 x 9.84 x 11.22"
385 x 250 x 285 mm
18.11 x 10.24 x 11.22"
460 x 260 x 285 mm
Weight - Shipping 19.8 lbs
9.0 Kgs
26.0 lbs
11.8 Kgs
36.4 lbs
16.5 Kgs
41.4 lbs
18.8 Kgs